Views: 214 Author: Capital Technology Publish Time: 2026-10-28 Origin: Site
Content Menu
● Why Choose a San Ace Counter Rotating Fan?
● Understanding Airflow and Static Pressure Before Comparing Models
>> Airflow: The Volume of Air Available for Cooling
>> Static Pressure: The Ability to Overcome Resistance
● How to Read a San Ace Fan Performance Curve
● A Five-Step Process for San Ace Counter Rotating Fan Selection
>> Step 1: Define the Thermal Requirement
>> Step 2: Measure or Estimate System Resistance
>> Step 3: Compare Candidates at the Required Duty Point
>> Step 4: Check PWM Control and Monitoring
>> Step 5: Validate Inside the Finished Equipment
● San Ace Counter Rotating Fan Specifications: A Practical Comparison
>> Why the Larger Fan Does Not Automatically Win
>> What the 9CRH Development Actually Demonstrates
● Worked Example: Turn a Cooling Requirement into a Fan Shortlist
● Expert Insight: Optimize Power and Noise at Equal Cooling Duty
● Build Reliability into the Selection Specification
>> Interpret Expected Life Correctly
>> Treat Fault Performance as a Separate Test
● Selecting with Capital Technology Co., Limited
>> 1. Should I Prioritize Airflow or Static Pressure?
>> 2. Can Maximum Airflow and Maximum Static Pressure Occur Together?
>> 3. Is a Counter Rotating Fan Always Better Than a Standard Axial Fan?
>> 4. Can I Select a Fan Using Only Its CFM Rating?
>> 5. Does PWM Control Eliminate the Need for Thermal Testing?
>> 6. What Information Should I Provide When Requesting a Recommendation?
Choosing a San Ace counter rotating fan by airflow and static pressure starts with one essential question: how much air will the fan actually move through your equipment? Maximum CFM alone cannot answer it. Neither can maximum static pressure. The correct choice depends on the fan's performance curve, the resistance of your enclosure, and the airflow needed to control component temperatures.
At Capital Technology Co., Limited, our selection philosophy is straightforward: define the cooling requirement before comparing part numbers. As a cooling solutions manufacturer with the CAPITAL brand and a SANYO DENKI distribution business, we approach fan selection as a system-design decision—not simply a catalog comparison.
This guide explains how to evaluate San Ace counter rotating fans, interpret performance data, and build a practical shortlist for demanding electronics.

A counter rotating fan combines two impellers arranged in series and rotating in opposite directions. The stages work together to produce airflow against substantial resistance.
This architecture is particularly relevant when air must pass through densely packed components, restrictive heat sinks, filters, or narrow ventilation paths.
SANYO DENKI identifies servers, storage systems, ICT equipment, and power supplies as applications for its counter rotating products.
However, a counter rotating fan is not automatically the best solution for every enclosure. If the airflow path has little resistance, a conventional axial fan may satisfy the requirement with less installation depth or a different acoustic profile.
The practical question is not whether counter rotation sounds more powerful. It is whether its pressure–airflow performance matches your system.
Airflow describes the volume of air moved per unit of time. Fan specifications commonly express it in:
- Cubic feet per minute: CFM.
- Cubic meters per minute: m³/min.
Airflow transports heat away from components. However, catalog maximum airflow normally represents operation near zero external static pressure.
Once you install a fan behind a filter or heat sink, resistance reduces the delivered airflow. A fan advertised at 90.8 CFM will not necessarily deliver 90.8 CFM inside your equipment.
Static pressure indicates the pressure difference a fan can develop. Common units include pascals and inches of water.
Maximum static pressure occurs at the opposite end of the performance curve from maximum airflow: approximately zero delivered airflow.
These two catalog maxima are separate endpoints, not simultaneous operating conditions.
The most important selection concept is the operating point: the airflow and pressure where the fan curve intersects your system resistance curve.
A pressure–airflow curve, often called a P–Q curve, shows the relationship between delivered airflow and static pressure.
Airflow normally appears on the horizontal axis. Static pressure appears on the vertical axis.
Your enclosure also has a resistance curve. SANYO DENKI describes an approximate relationship as:
ΔP=KQ2
Here, ΔP is pressure loss,Q is airflow, and K represents the resistance of the equipment.
This approximation explains an important design relationship: demanding more airflow through an unchanged restrictive path requires disproportionately more pressure.
To evaluate a candidate:
1. Establish the required airflow.
2. Determine system pressure loss at that airflow.
3. Locate that requirement on the P–Q graph.
4. Check whether the fan curve supports the requirement.
5. Verify the actual intersection with the system curve.
Do not draw a straight line between catalog maxima and treat it as the real fan curve. Use the manufacturer's published performance data.

Begin with heat dissipation, maximum inlet temperature, and acceptable temperature rise.
A first-pass sensible-heat balance is:
Qv=Pheat/ρcpΔT
In this equation:
- Qv is volumetric airflow in m³/s.
- Pheat is heat transferred to the airflow in watts.
- ρ is air density.
- cp is air's specific heat capacity.
- ΔT is the permitted air-temperature rise.
This is a preliminary estimate, not a substitute for component-level thermal validation. Air bypass, uneven distribution, and local hot spots can make acceptable bulk airflow insufficient.
Include the complete airflow path:
- Inlet and outlet openings.
- Filters and protective guards.
- Heat sinks and circuit boards.
- Internal partitions and ducts.
- Cable bundles and connectors.
Prototype measurement is more useful than selecting from enclosure dimensions alone. SANYO DENKI's Airflow Tester technical report specifically describes measuring system impedance to identify suitable fans.
Also evaluate more than the clean, unobstructed condition. If filter loading is expected, define a realistic service-limit condition.

Choose fans that satisfy the airflow requirement at the corresponding pressure—not fans that merely have impressive maximum values.
A useful comparison sheet includes:
| Selection item | What to verify |
|---|---|
| Required airflow | Delivered airflow through the relevant cooling path |
| Required pressure | Resistance at the target airflow |
| Fan curve | Performance at the intended voltage and control setting |
| Mechanical fit | Frame dimensions, depth, mounting, and clearance |
| Electrical fit | Supply range, input power, connector, and wiring |
| Validation criteria | Component temperature, acoustics, and fault behavior |
The right shortlist contains models that meet the same cooling duty, making subsequent comparisons meaningful.
Where available, pulse-width modulation allows fan speed to respond to cooling demand.
Verify model-specific requirements for:
- PWM frequency and input characteristics.
- Minimum operating speed.
- Behavior at low or zero duty cycle.
- Speed-sensor outputs.
- Startup and fault detection.
Do not assume every San Ace counter rotating fan uses identical control behavior or wiring. Confirm the exact part number and connector specification.
Test with the actual enclosure, covers, filters, guards, and cable arrangement.
Measure critical component temperatures, inlet temperature, airflow where practical, and electrical consumption.
Repeat testing under representative worst-case conditions. A catalog-qualified fan can still underperform if the installation blocks its inlet or allows cooling air to bypass the hottest components.

The following manufacturer-published examples illustrate why airflow and static pressure must be evaluated together.
| Model | Dimensions | Rated voltage | Maximum airflow | Maximum static pressure | Rated input |
|---|---|---|---|---|---|
| 9CRH0612P6G001 | 60 × 60 × 56 mm | 12 VDC | 2.57 m³/min / 90.8 CFM | 3,350 Pa | 67.2 W |
| 9CRA0912P0G001 | 92 × 92 × 76 mm | 12 VDC | 5.8 m³/min / 205 CFM | 1,650 Pa | 108.0 W |
These are specification examples, not a direct replacement recommendation. Confirm current documentation and availability before procurement.
The 92 mm example has substantially higher maximum airflow. The 60 mm example has substantially higher maximum static pressure.
Neither fact independently establishes which fan will deliver more useful cooling in a particular enclosure. That requires comparing their curves against the same system resistance.
Packaging also matters. A mechanically incompatible fan is not a valid candidate, regardless of its performance.
In its June 2024 announcement, SANYO DENKI reported that the 60 mm 9CRH achieved approximately 2.9 times the maximum static pressure and about 12% more maximum airflow than the specified 9CRA0612P6K001 comparison model.
That is a defined, same-size product comparison—not evidence that every 9CRH model outperforms every alternative under every condition.
Consider an illustrative electronics enclosure requiring 1.5 m³/min of airflow. Suppose prototype testing indicates a pressure loss of 500 Pa at that flow.
Your preliminary selection target is therefore:
- Airflow: 1.5 m³/min.
- Static pressure: 500 Pa.
A fan with maximum airflow above 1.5 m³/min might still fail to deliver the required flow against 500 Pa.
Similarly, a fan with maximum static pressure above 500 Pa might not sustain enough pressure at 1.5 m³/min.
Request the actual P–Q curves and overlay the measured system resistance curve. Then check the resulting operating airflow.
Next, repeat the comparison for the service-limit filter condition and relevant supply conditions.
These figures illustrate a selection method. They are not measured CAPITAL customer results or a confirmed recommendation for either example model.
A common procurement mistake is comparing two fans at full speed when they deliver different amounts of useful cooling.
The better comparison asks: which candidate meets the same thermal requirement with lower power consumption and acceptable sound?
SANYO DENKI's published Airflow Tester example demonstrates this distinction. Two candidate fans met the required cooling condition, but the preferred fan reduced sound pressure level by 4 dB(A) and power consumption by 4.2 W.
This is a manufacturer's documented example, not a universal saving.
For your project, compare power and acoustics at the selected operating condition. Full-speed catalog values alone do not show the complete tradeoff.
For the cited 9CRH product, SANYO DENKI specifies an expected life of 40,000 hours under stated conditions: continuous free-air operation at 60°C and rated voltage, with an L10 survival basis.
L10 means 90% survival under those specified conditions. It does not guarantee that every installed unit will operate for 40,000 hours.
Check the exact model's temperature limits and life conditions rather than transferring a family-level assumption to every part number.
A two-stage counter rotating assembly should not automatically be treated as redundant cooling.
If continued operation after a fault matters, define the required residual cooling and test the relevant failure conditions. Verify monitoring behavior and the equipment's shutdown or protective response.
Normal-operation airflow does not establish fault-tolerant performance.
Capital Technology Co., Limited supplies DC fans, AC fans, and cooling solutions under its CAPITAL brand and through its SANYO DENKI business.
According to the company background supplied for this article, CAPITAL is SANYO DENKI's chief agent and has become a supplier to ZTE, HUAWEI, and HYTERA. These commercial credentials are company-provided statements; they do not replace application-specific technical validation.
For a focused selection review, send CAPITAL:
- Heat dissipation and maximum inlet temperature.
- Available fan dimensions and supply voltage.
- Target airflow and measured pressure loss.
- Filter, duct, and enclosure information.
- Noise, control, and monitoring requirements.
- Sample quantity and production schedule.
Request a San Ace counter rotating fan shortlist with exact part numbers, relevant P–Q curves, electrical details, and a prototype validation checklist. This makes the discussion specific enough to support an engineering decision.
Prioritize the combination required by your system. Airflow supports heat removal, while pressure capability allows that airflow to pass through resistance. Select at the operating point rather than prioritizing either maximum independently.
No. Maximum airflow is measured near zero external static pressure. Maximum static pressure occurs near zero airflow. Actual operation lies elsewhere on the performance curve.
No. Counter rotating designs are useful for demanding pressure requirements, but a conventional axial fan may satisfy a less restrictive application. Compare cooling duty, installation space, controls, power, and acoustics.
No. CFM without the associated pressure condition cannot establish installed performance. Obtain the P–Q curve and compare it with your enclosure's resistance.
No. PWM adjusts speed; it does not verify airflow distribution or component temperature. Validate the control strategy under representative loads, ambient conditions, and fault scenarios.
Provide heat load, ambient temperature, fan space, voltage, airflow target, pressure-loss data, and acoustic limits. Include enclosure drawings and control requirements where available.
1. SANYO DENKI. "Development of the 'San Ace Airflow Tester'—A Measuring Device for System Impedance and Operating Airflow of Equipment." Technical Report No. 42, November 2016. Basis for system resistance, operating-point selection, and the documented power/acoustic comparison. [Read the technical report]. [sanyodenki]
2. SANYO DENKI. "SANYO DENKI Develops 60 × 60 × 56 mm Counter Rotating Fan with the Highest Static Pressure and Airflow in the Industry." June 12, 2024. Basis for the 9CRH specifications, defined predecessor comparison, and expected-life conditions. [Read the product announcement]. [sanyodenki]
3. SANYO DENKI. "SANYO DENKI Releases 92 × 92 × 76 mm Counter Rotating Fan: Outstanding Airflow and Static Pressure." May 25, 2016. Basis for the 9CRA model specifications, applications, and PWM availability. [Read the product announcement]. [sanyodenki]
4. SANYO DENKI. "Counter Rotating Fan—San Ace Product Lineup." Product-family context and model-dependent specifications. [Explore the product lineup]. [products.sanyodenki]